| Plan Review Notes For Permit 15020214 |
| Permit Number |
15020214 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-10 09:27:48 | 1) THE TYPE OF PIPE TO BE USED FOR THE GAS LINE IS | | | SHOWN AS 3/4" TYPE L COPPER. SECTION G2414.5.2 OF THE | | | 2010 FBCR PROHIBITS THE USE OF COPPER IF THE GAS | | | CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN | | | SULFIDE PER 100 STANDARD CUBIC FEET OF GAS. | | | VERIFICATION FROM THE GAS PURVEYOR SHALL BE SUBMITTED | | | AS TO THE AMOUNT OF HYDROGEN SULFIDE CONTAINED IN THE | | | GAS PER 100 CU. FT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|