 PROJECT: RESIDENTIAL RENNOVATION
 PERMIT#: 15020165
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 408.4
 PROVIDE A PANEL SCHEDULE INDICATING NEW AND EXISTING
 CIRCUITS, INCLUDING BREAKER, AND WIRE SIZE AND TYPE.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE.
  
 2) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 3) NEC 220.16(2)
 PROVIDE AN ACCURATE LOAD CALCULATION WITH ALL NEW AND
 EXISTING LOADS. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH ARTICLE 220 OF THE NEC.
  
 4)WPB AMENDMENTS TO FBC 107.2.1
 PROVIDE CIRCUIT NUMBERS AND WIRE SIZES ON THE FLOOR
 PLAN FOR ANY AND ALL NEW WORK. CIRCUITS AND WIRE SIZES
 INDICATED ON THE FLOOR PLAN TO CORESPOND TO THE PANEL
 SCHEDULE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  