| 2015-06-03 09:36:30 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED (SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION). |
| | A) FORM 402-2010 CAN NOT BE USED IF THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SEE GENERAL INSTRUCTIONS NOTE #1 |
| | ON TOP OF FORM SUBMITTED. |
| | |
| | B) COMPLETE ALL THE INFORMATION ON TABLE 402A ON PAGE 2 |
| | OF FORM SUBMITTED. THE INSTALLED VALUES MUST MEET OR |
| | EXCEED THE PERFORMANCE CRITERIA. AND, REVISE ALL THE |
| | INFORMATION ON PAGE ONE OF FORM SUBMITTED. SEE GENERAL |
| | INSTRUCTION #2 ON TOP OF FORM SUBMITTED. |
| | |
| | C) REVISE ITEM #6C. GLASS AREA TO MATCH PLANS. NEED TO |
| | INCLUDE ALL NEW WINDOWS AND EXISTING WINDOWS. |
| | |
| | D) REVISE ITEM #9. WALL TYPE DOESN'T MATCH PLANS. |
| | |
| | E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| | AMENDMENTS TO FBC. PROVIDE COPY OF SIGNED CONTRACT FOR |
| | THE CONSTRUCTION AND DESIGN PROFESSIONAL FEES. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | 3- CLARIFY WHY SUBMITTING NOA 11-1013.14 FOR SINGLE |
| | HUNG WINDOWS. THERE IS NOT SINGLE HUNG WINDOWS ON THIS |
| | PROJECT. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- EXTERIOR BLOCK WALL SECTION 1/A.01: |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK |
| | WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE |
| | WITH THE ENERGY CALCULATIONS, INCLUDING THE CEILING R |
| | VALUE. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | REVISED WALL SECTION DOESN'T COMPLY. |
| | R-VALUE GIVEN TO THE WALL IS FOR THE R-VALUE OF THE |
| | ADDED INSULATION ONLY. "THE R-VALUES OF STRUCTURAL |
| | BUILDING MATERIALS SUCH AS FRAMING MEMBERS, CONCRETE |
| | BLOCKS OR GYPSUM BOARD SHALL NOT BE INCLUDED.". SEE |
| | SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: 3/4" DOW "TUFF-R" PROVIDES ONLY R-5 VALUE. |
| | PROVIDE ICC EVALUATION REPORT FOR THIS TYPE OF |
| | INSULATION SHOWING COMPLIANCE WITH SEC. R316. KEEP IN |
| | MIND THAT THIS PRODUCT IS USUALLY INSTALLED ON THE |
| | EXTERIOR SIDE OF THE WALL. SEE ESR-3089 REPORT. REVISE |
| | WALL SECTION DETAIL AS REQUIRED. |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |