| 2015-05-18 15:01:49 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | NOTE: ENERGY CALCULATIONS AND EQUIPMENT LOAD |
| | CALCULATIONS ARE TWO DIFFERENT THINGS. THE PERMIT CAN |
| | NOT BE ISSUED WITHOUT THE ENERGY CALCULATIONS |
| | COMPLIANCE CERTIFICATION. SEC. 103.2.3.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| | AMENDMENTS TO FBC. PROVIDE COPY OF SIGNED CONTRACT FOR |
| | THE CONSTRUCTION AND DESIGN PROFESSIONAL FEES. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE PRE-CAST LINTEL FOR NEW FIXED |
| | WINDOW. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- EXTERIOR BLOCK WALL SECTION 1/A.01: |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK |
| | WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE |
| | WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. REVISED WALL SECTION DOESN'T |
| | COMPLY. |
| | R-VALUE GIVEN TO THE WALL IS FOR THE R-VALUE OF THE |
| | ADDED INSULATION ONLY. "THE R-VALUES OF STRUCTURAL |
| | BUILDING MATERIALS SUCH AS FRAMING MEMBERS, CONCRETE |
| | BLOCKS OR GYPSUM BOARD SHALL NOT BE INCLUDED.". SEE |
| | SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |