| 2015-02-24 15:45:33 | ****CORRECTIONS**** | | | ****REVISED 2/26 AND EMAILED APPLICANT**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE SOFFIT OPTION SELECTED HAS A DP LIMITATION OF +? | | | / -64.4 PSF. FOR 10SF (AREA TRIBUTARY TO A FASTENER), | | | 20' MRH, EXPOSURE D, DESIGN PRESSURES REQUIRED ARE | | | +48.5/-52.6 FOR ZONE 4, AND +48.5/-65PSF FOR ZONE 5. | | | CONTRACTOR HAS SELECTED A SYSTEM WHICH DOES NOT HAVE A | | | POSITIVE DESIGN PRESSURE LIMITATION (PLEASE CONTACT | | | MANUFACTURER OR INDICATE WHERE IN THE PRODUCT APPROVAL | | | THIS IS ADDRESSED) AND DOES NOT MEET THE NEGATIVE | | | PRESSURE FOR ZONE 5. | | | | | | OBTAINING THE EXACT MRH AND/OR OBTAINING ENGINEERING | | | MAY RESULT IN LOWER PRESSURES. | | | | | | FBC 2010 RESIDENTIAL 301 | | | | | | **PLEASE ADVISE VIA EMAIL WHEN THIS IS RESUBMITTED - | | | REVIEW WILL BE DONE TIMELY** | | | | | | ***2/26 - NEGATIVE DP FOR MRH20', ZONE5, 169MPH IS | | | -64.75PSF (DOES NOT MEET REQUIREMENT OF -64.4; PLEASE | | | VERIFY MRH OR OBTAIN ENGINEERING)*** | | | |
|