| 2015-02-13 11:16:07 | BUILDING PLAN REVIEW |
| | REVISION:15020080 |
| | PERMIT: 12040478 |
| | ADD: 6651 N. JOG RD. |
| | CONT:KBR |
| | TEL: ( |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) SHEET 200-A20-005 FLOOR PLAN @ ELEVATION 170'-4" |
| | SHOWS A DOOR IN THE VERTICAL EXIT STAIRWAY THAT LEADS |
| | DIRECTLY INTO THE SERVICE ELEVATOR MACHINE ROOM. PLEASE |
| | PROVIDE COMPLIANCE WITH: |
| | 2010 FBC-B 1022.3 OPENINGS AND PENETRATIONS. |
| | EXIT ENCLOSURE OPENING PROTECTIVES SHALL BE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715. |
| | OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED |
| | EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| | FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| | SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| | |
| | 2010 FBC-B 1022.4 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 2A) THERE IS 2 PLANS 300-A20-001 THE NORTHWEST STAIR |
| | AND SHEETS 300-A20-006 THE SOUTHEAST STAIR, BOTH SHOW A |
| | GUARDRAIL SYSTEM OPEN AS ALLOWED FOR FACTORY/ |
| | INDUSTRIAL OCCUPANCIES. THERE WAS A MEETING IN THE |
| | BUILDING DEPARTMENT CONFERENCE ROOM WITH THE |
| | CONTRACTOR, THE THRESHOLD INSPECTORS AS TO WHERE THESE |
| | TYPE OF GUARDRAIL SYSTEMS CAN BE INSTALLED. THE CONCERN |
| | IS NOW THERE ARE VISITORS BEING ALLOWED INTO THE BOILER |
| | BUILDING ON THERE WAY TO THE CONTROL ROOM. THE (2) |
| | REQUIRED EXITS AS DISCUSSEED IN THE MEETING HAD TO MEET |
| | THE MORE RESTRICTIVE GUARDRAIL / HANDRAIL REQUIREMENTS |
| | MEETING THE OPENING LIMITATIONS OF 2010 FBC-B 1013.3, |
| | NO EXCEPTIONS CAN BE TAKEN. IDENTIFY WHICH STAIRWELLS |
| | WILL MEET THIS REQUIREMENT. |
| | THE OTHER ISSUE WAS |
| | |
| | 2B) THE FIRE DEPARTMENT ON THEIR JOBSITE INSPECTION |
| | VISITS HAS ALSO FOUND THE GUARDRAILS IN VAROIUS |
| | STAIRWWELLS DIDN'T MEET THE HEIGHT REQUIREMENT OF 42 |
| | INCHES FOUND IN FBC-B 1013.3. THERE HAS NEVER BEEN ANY |
| | EXCEPTIONS FROM EITHER THE FIRE DEPAARTMENT NOR THE |
| | BUILDING DEPARTMENT FOR THE HEIGHT REQUIREMENTS. |
| | |
| | 2C) SHEET 200-A9.2 SECTION # 3 DOES NOT SHOW ANY |
| | HANDRAILS IN EITHER THE FLOOR PLAN OR ELEVATION VIEWS. |
| | SHOW COMPLIANCE WITH 2010 FBC-B 1012.2. |
| | |
| | 3) BUILDING PROVISO: SHEET 300-20-007 SHOWS AN ACCESS |
| | DOOR (WEST ELEVATION) AT THE ELEVATOR MACHINE ROOM, |
| | ELE. 170'-4". THIS LOCATION SHALL BE AN APPROVED MEANS |
| | OF ACCESS. FBC-B 3006.1 ACCESS. AN APPROVED MEANS OF |
| | ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS AND |
| | OVERHEAD MACHINERY SPACES. |
| | |
| | THIS ACCESS DOOR SHALL BE LARGE ENOUGH FOR THIS ACCESS |
| | ARE MAINTENANCE, REPLACEMENT OF EQUIPMENT AND THE |
| | NECESSARY STATE AND LOCAL INSPECTION TO BE PREFORMED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |