| Plan Review Notes For Permit 15020073 |
| Permit Number |
15020073 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-10 10:34:59 | PLAN DENIED | | | 1) PROVIDE DUCT SIZE ON PLAN, | | | PROVIDE CAN AND GRILL SIZE ON PLAN | | | PROVIDE CFM ON EACH SUPPLY DUCT. | | | PER SECTION 107 FBC 2010 | | | 2) SHOW LOCATION OF RETURN AIR ON PLANS. | | | PER SECTION 107 FBC 2010 | | | 3) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR 2010 FBC (M) | | | 4) REFER TO SECTION 601.4 MATERIALS | | | WITHIN PLENUM'S INCLUDING CLOSET DOOR | | | AND CONDENSATE LINE 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|