| 2015-02-11 11:16:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE PLANS WERE NOT STAPLED OR SEALED TOGETHER. THE |
| | PALNS SHALL BE SUBMITTED STAPLED OR SEALED TOGETHER TO |
| | NOT BE SEPARATED. |
| | |
| | SHEET C - 1 HAS AN INCORRECT ADDRESS IN THE ENGINEER |
| | COLUMN NOTED AS MIAMI, PLEASE DELETE AND CORRECT. |
| | |
| | SHEET C - 1 HAS THE INCORRECT EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE AS 2010. IT SHOULD INDICATE THE |
| | 2012 EDITION OF NFPA 1 AND 101. |
| | |
| | ALL CONSTUCTION SHALL COMPLY WITH THE REQUIRMENTS OF |
| | NFPA 101, CHAPET 43, BUILDING REHABILITATION, SECTION |
| | 43.6 RECONSTRUCTION. |
| | |
| | PER NFPA 101 43.6.4.1 IN A BUILDING WITH REHABILITATION |
| | WORK AREAS INVOLVING OVER 50 PERCENT OF THE AGGREGATE |
| | BUILDING AREA, AUTOMATIC SPRINKLER SYSTEMS SHALL BE |
| | PROVIDED ON THE HIGHEST FLOOR CONTAINING REHABILITATION |
| | WORK AREA AND ON ALL FLOORS BELOW IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF OTHER SECTIONS OF THIS CODE |
| | APPLICABLE TO NEW CONTRUCTION FOR THE OCCUPANCY. THIS |
| | OCCUPANCY SHALL MEET THE REQUIREMENTS OF NFPA 101, |
| | CHAPTER 30 NEW APARTMENT BUILDINGS.THE FIRE SPRINKLER |
| | SYSTEM SHALL BE SUPERVISED PER NFPA 30. |
| | |
| | PER SECTION 43.6.2.2 ILLUMINATION, EMERGENCY LIGHTING |
| | AND MARKING OF MEANS OF EGRESS, 43.6.2.2.2 WHERE THE |
| | RECONSTRUCTION REHABILITATION WORK AREA ON ANY FLOOR |
| | EXCEEDS 50 PERCENT OF THEAT FLOOR AREA, MEANS OF EGRESS |
| | THROUGHOUT THE FLOOR SHALL BE PROVIDED WITH |
| | ILLUMINATION, EMERGENCY LIGHTING AND MARKING OF MEANS |
| | OF EGRESS IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER |
| | SECTIONS OF THIS CODE APPLICABLE TO NEW CONTRUCTION FOR |
| | THE OCCUPANCY. |
| | |
| | PER SECTION 43.6.5 FIRE ALARM SYSTEMS - SMOKE ALARMS, |
| | 43.6.5.1 IN LODGING OR ROOMING HOUSES, HOTELS, AND |
| | DORMITORIES, AND APARTMENT BUILDINGS, INDIVIDUAL |
| | SLEEPING ROOMS, GUEST ROOMS, AND DWELLING UNITS WITHIN |
| | REHABILITATION WORK AREA SHALL BE PROVIDED WITH SMOKE |
| | ALARMS COMPLYING WITH THE REQUIRMENTS OF OTHER SECTIONS |
| | OF THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE |
| | OCCUPANCY. |
| | |
| | THE CONSTUCTION SHALL COMPLY WITH NFPA 101, CHAPTER 30, |
| | NEW APARTMENT BUILDINGS. |
| | |
| | EMERGENCY LIGHTING IS REQUIRED AT EACH PORCH AREA. EXIT |
| | SIGNAGE IS REQUIRED AT THE SECOND FLOOR LEVEL PORCH |
| | AREA. |
| | |
| | EACH ENTRY DOOR IN THE FIRST AND SECOND FLOOR AREA IS |
| | REQUIRED TO HAVE NOT LESS THAN A 20 MINUTE FIRE |
| | PROTECTION RATING AND SHALL BE SELF CLOSING AND |
| | LATCHING. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |