| 2015-02-05 11:02:32 | 2/5/2015 |
| | PROJECT: 513 SAPODILLA |
| | PERMIT#: 15020073 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CHANGE TITLE BLOCK ON COVER SHEET TO CORRECT THE |
| | PROJECT ADDRESS. WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 2) PROVIDE FAULT CURRENT RATING CALCULATION AND VERIFY |
| | THE ELECTRICAL SERVICE HAS A FAULT CURRENT RATING THAT |
| | IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE |
| | CURRENT THAT MUST BE INTERRUPTED. NEC 110.9 |
| | |
| | 3) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORESPONDING TO THE PANEL DIRECTORY. WPB AMENDMENTS TO |
| | FBC 107.2.1 |
| | |
| | 4) PROVIDE DISCONNECTS WHERE REQUIRED FOR EQUIPMERNT |
| | SUCH AS WATER HEATER AND AHU. WPB AMENDMENTS TO FBC |
| | 107.2.1 |
| | |
| | 5) PROVIDE SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. SMOKE DETECTOR REQUIRED OUTSIDE OF SLEEPING |
| | ROOMS. FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 6) ADD A NOTE FOR THE LUMINAIRES IN CLOTHES CLOSETS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF |
| | THE NEC 410.16(A) AND (B). |
| | |
| | 7) PROVIDE A LIGHT FOR THE STAIRS THAT CAN BE CONTROLED |
| | FROM THE TOP OR BOTTOM LANDINGS. FBC 1205.4, 1205.5, |
| | 1006.1, NEC 210.70 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |