| Plan Review Notes For Permit 15020068 |
| Permit Number |
15020068 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-07-07 09:31:31 | AFTER A DISCUSSION W/THE GC & EC, IT WAS DETERMINED | | | THAT THE ELECTRICAL DRAWING SUBMITTED FOR PERMITTING | | | WENT WAY BEYOND THE INTENDED SCOPE OF THE JOB WHICH IS | | | ONLY TO RETURN THE WATER HEATER TO ITS ORIGINAL | | | LOCATION AND CONNECTED TO THE EXISTING CIRCUIT. ADD THE | | | CEILING GFCI OUTLET FOR THE GARAGE DOOR OPENER AND AN | | | ADDITIONAL GFCI OUTLET IN THE GARAGE. | | | PER NEC & FBC REQUIREMENTS, ALL GARAGE OUTLETS SHALL BE | | | GFCI PROTECTED. ALL NEW INSTALLATIONS SHALL BE | | | ARC-FAULT PROTECTED. PER FBC-R314-315 SMOKE DETECTOR | | | COMPLIANCE IS MANDATED. CO DETECTION AS PER FBC-315 IS | | | REQUIRED. | | | | | | THIS PERMIT IS READY TO BE ISSUED WITH THE PROVISO TO | | | SUBMIT A CORRECTED AS-BUILT PLANS FOR APPROVAL PRIOR TO | | | THE FIRST ELECTRICAL INSPECTION. |
|