| 2015-06-24 14:26:56 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | 1. PER NFPA 72 ? 29.8.3.4(4), SMOKE DETECTORS SHALL NOT |
| | BE INSTALLED WITHIN 3? FROM THE TIP OF A CEILING FAN |
| | BLADE OR ANY OTHER SOURCE OF FORCED AIR (A/C VENT OR |
| | RETURN). |
| | 2. PER FBC-R ? 315, YOU SHALL INSTALL A CO (CARBON |
| | MONOXIDE) DETECTOR WITHIN 10? OF THE BEDROOM DOOR. |
| | THEREFORE THE CEILING DETECTOR IN THE VESTIBULE OUTSIDE |
| | THE BEDROOMS SHALL BE A COMBINATION UNIT. |
| | 3. PER NEC 230.70, YOU SHALL HAVE A DISCONNECT ON THE |
| | OUTSIDE OF THE STRUCTURE OR AT A POINT NEAREST THE |
| | ENTRY THERETO. IN YOUR CASE ADJACENT TO THE SERVICE |
| | METER WILL DO. |
| | 4. PER NEC 440.14, THE DISCONNECT FOR THE RELOCATED AHU |
| | SHALL BE READILY ACCESSIBLE. |
| | 5. CONFIRM THE NEED FOR ?NOTE 21?, OF THE GENERAL |
| | NOTES. |
| | 6. CORRECT CONDUCTOR INSULATION AS INDICATED ON ?NOTE |
| | 28? OF GENERAL NOTES. |
| | 7. CORRECT THE RISER DIAGRAMS TO INCLUDE THE REQUIRED |
| | SERVICE DISCONNECT AND RENAME PANEL ?A? AS ?RELOCATED? |
| | RATHER THAN ?EXISTING?. |
| | 8. CORRECT ?NOTE 2? OF NOTE (). |
| | 9. PER NEC 210.52(C), THE KITCHEN OUTLETS ARE INDICATED |
| | ON THE DRAWING ARE NOT COMPLIANT WITH MINIMUM CODE |
| | REQUIREMENTS. |
| | |