| Plan Review Notes For Permit 15020047 |
| Permit Number |
15020047 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-01 04:35:58 | 1) SHOW THE LOCATION OF THE GAS DRYER ON THE PLAN.WPB | | | AMEND. TO 2010 FBC SEC.107.2.1. | | | 2) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES.WPB | | | AMEND. TO 2010 FBC SEC.107.2.1. 2ND REQUEST. | | | 3) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER | | | 2010 FBCR SEC.G2404.3. 2ND REQUEST. | | | 4) SUBMIT 2 COPIES OF THE APPLICABLE PIPE SIZING TABLE | | | FROM CHAPT.24 OF THE 2010 FBCR. 2ND REQUEST | | | 5) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM.2010 FBCR SEC,G2413.1., | | | 2413.2.2ND REQUEST. | | | 6) SHOW THE DISTANCE FROM THE METER TO THE FURTHEST OUT | | | PER 2010 FBCR SEC.G2413.4.1.2ND REQUEST. | | | 7) THE PERMIT APPLICATION WORK DESCRIPTION INCLUDES A | | | GAS DRYER TO BE INSTALLED BUT IT IS NOT SHOWN ON THE | | | GAS PLAN. CLARIFY. | | | 8) THE "SPECIFICATIONS" THAT WERE SUBMITTED ARE NOT | | | ACCEPTABLE. THEY LACK THE REQUIRED INFORMATION | | | NEEDED.WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 9) A SEPARATE ELECTRICAL PERMIT WILL BE REQUIRED FOR | | | THE TANKLESS WATER HEATER FOR THE AUTO IGNITER. | | | | | | I SUGGEST YOU CONTACT ME TO SET UP AN APPOINTMENT TO | | | REVIEW THE COMMENTS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|