| Plan Review Notes For Permit 15020033 |
| Permit Number |
15020033 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-19 16:59:29 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE INSTALLATION DRAWINGS THAT WERE SUBMITTED WITH | | | THE MULLIONS (NOA NO. 11-1031.07) WERE NOT SHRUNK TO | | | FIT ON THE SMALLER 8.5" X 11" PAPER AND PARTS OF THE | | | INFORMATION IS MISSING FROM EACH PAGE. SUBMIT TWO SETS | | | OF DRAWINGS THAT ARE COMPLETE. FBC 107.2.1 & DCA RULE | | | 9N-7 | | | | | | 2) THE PRODUCT APPROVALS FOR THE FIXED WINDOW THAT WERE | | | SUBMITTED (NOA NO.14-0515.11) ARE ONLY RATED FOR SMALL | | | MISSILE IMPACT. THEY ARE REQUIRED TO HAVE IMPACT | | | PROTECTION DEVICES FOR LARGE MISSLE IMPACT. FBC R | | | 301.2.1.2 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS | | | FOR THE IMPACT PROTECTION DEVICES ALONG WITH AN | | | INSTALLATION SCHEDULE. | | | |
|