| Date |
Text |
| 2015-04-10 11:05:22 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PHASE 2 OF THIS PROJECT (WINDOWS AND DOORS) WAS |
| | ADDED ON 3/11/15. PLEASE UPDATE VALUATION DECLARED IN |
| | THE PERMIT APPLICATION AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS TO FBC. PLEASE PROVIDE COPY OF SIGNED |
| | CONTRACT FOR THE OVERALL SCOPE OF WORK. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- SHEET A-2: |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH |
| | ALL THE REQUIREMENTS OF SEC. R311.7.7 AND SEC. R312 OF |
| | 2010 FBC-RESIDENTIAL. ALSO, PROVIDE COMPLETE DETAILS |
| | AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE |
| | LOAD REQUIREMENTS OF TABLE R301.5 OF 2010 |
| | FBC-RESIDENTIAL. REPEAT COMMENT. "GUARDRAIL/HANDRAIL |
| | DETAILS" SUBMITTED DOESN'T MATCH PLANS. THERE ARE NOT |
| | DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| | HANDRAIL AND GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE |
| | LOAD OF TABLE R301.5. GUARDRAIL HEIGHT IS DIMENSIONED |
| | AS 36", WHILE GUARDRAIL NOTE STATES 42". REVISE AS |
| | REQUIRED TO MATCH. SEC. 1608.2 SPECIFIED ON GUARDRAIL |
| | DETAIL DOESN'T APPLY TO SINGLE FAMILY RESIDENCE (R3). |
| | THAT SECTIONS APPLIES TO THE BUILDING CODE NOT THE |
| | RESIDENTIAL CODE. BESIDES THAT SECTION IS "RESERVED". |
| | REVISE AS REQUIRED. |
| | |
| | 3- PROVIDE COMPLETE SHORING DETAILS AND SPECIFICATIONS |
| | FOR THE INSTALLATION OF THE NEW STEEL COLUMNS. SEC. |
| | 107.2.1.3 CITY AMENDMENTS. REPEAT COMMENT. NOT |
| | ADDRESSED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY |
| | WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT |
| | APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS |
| | ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301. |
| | NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL |
| | FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT |
| | WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW |
| | CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF |
| | CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE |
| | APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT |
| | CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE, |
| | THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS. |
| | ONLY ONE WAS SUBMITTED. REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS |
| | #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285 |
| | SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE |
| | BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED. |
| | PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT |
| | APPROVAL THAT COVERS DOORS #1 AND #8. REPEAT COMMENT. |
| | NOT ADDRESSED. |
| | |
| | E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE |
| | FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING |
| | THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| | APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. REPEAT |
| | COMMENT. NOT ADDRESSED. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND |
| | SUBMIT OLD PLANS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |