| Plan Review Notes For Permit 15020030 |
| Permit Number |
15020030 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-04 07:17:12 | 1) SHOW THE RELOCATED LAVATORY IN BATH #1 ON THE | | | SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) AS DRAWN, THE SANITARY RISER DOES NOT MEET CODE. THE | | | HORIZONTAL WET VENT HAS ONE TOO MANY LAVATORIES, ONE | | | TOO MANY SHOWERS AND EXCEEDS THE MAXIMUM NUMBER OF | | | FIXTURE UNITS FOR A 2" WET VENT PER TABLE P3108.3 OF | | | THE 2010 FBCR SEC. P3108. | | | 3) PLANS SHALL BEAR THE SEAL AND SIGNATURE OF THE | | | DESIGN PROFESSIONAL PER THE FL. ADMIN. RULE 61G15 | | | -23.002. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|