| 2015-02-26 12:41:09 | 15020030 | | | 1209 N. FLAGLER DR. | | | SF REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE AND | | | DISCONNECT ON THE BUILDING. VERIFY THE MAIN DISCONNECT | | | IS LOCATED AT THE POINT OF SERVICE. VERIFY THE | | | UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED IN THE | | | BUILDING. INCLUDE A PANEL SCHEDULE FOR EACH PANEL. NEC | | | 230.70(A)(1) | | | | | | ADD RECEPTACLES (DINING, WALL AT STAIRS, KITCHEN, | | | BEDROOM #3 AND #4) SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR | | | MORE IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND | | | REAR ELEVATIONS. NEC 210.8, 210.52(E)(1) | | | | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED ON BALCONY. NEC | | | 210.8, 210.52(E)(3) | | | | | | SWITCH CONTROLLED LIGHTING OUTLETS ARE REQUIRED AT ALL | | | ENTRANCES. NEC 210.70 (A) (2) (B) | | | | | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|