| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | IT IS NOT CLEAR IF THE ELECTRICAL SERVICE IS REPLACING |
| | AN EXISTING SERVICE OR IF A NEW ELECTRICAL SERVICE IS |
| | BEING PROPOSED. VERIFY THIS BUILDING/TENANT HAS |
| | SUFFICIENT FIRE SEPARATION TO QUALIFY AS A SEPARATE |
| | BUILDING AND TO HAVE ITS OWN ELECTRICAL SERVICE OR |
| | PROVIDE JUSTIFICATION FOR THE SERVICE PROPOSED. NEC |
| | 230.2, 215.5, 230.71 |
| | |
| | INDICATE THE REQUIRED FAULT CURRENT RATING FOR THE |
| | ELECTRICAL SERVICE AND PANELBOARDS. NEC 110.9, 110.10, |
| | |
| | ON THE ELECTRICAL PLAN PROVIDE A SAFETY LABELING |
| | SCHEDULE FOR FLASH PROTECTION FOR THE SERVICE, PANEL |
| | BOARDS AND MAIN DISCONNECTING MEANS. NEC 110.22 |
| | |
| | PROVIDE A PERMANENT IDENTIFICATION PLAQUE WHICH SHOWS |
| | THE LOCATION OF THE ELECTRICAL SERVICES AND MAIN |
| | DISCONNECTS FOR THIS MULTIPLE OCCUPANCY BUILDING. NEC |
| | 230.2 (E) |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF |
| | USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D) |
| | |
| | PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE |
| | LIMITATIONS AND VOLTAGE SEPARATION WITH BARRIERS |
| | REQUIRED FOR SWITCHES AND ADJACENT DEVICES. NEC 404.8 |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM |
| | SYSTEMS, SECURITY, VOICE AND DATA SYSTEMS. |
| | |