| Plan Review Notes For Permit 15020017 |
| Permit Number |
15020017 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-09 16:44:17 | 2/9/2015 | | | PROJECT: LAFAYETTES MISIC ROOM | | | PERMIT#: 15020017 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED. | | | | | | 1) PROVIDE EXIT AND EMERGENCY LIGHTING AS REQUIRED. SEE | | | NFPA 101 SECTION 7.10.1.5.1, NEC 700.16, NEC 700.12. | | | | | | 2) PROVIDE PANEL SCHEDULES WITH CIRCUIT NUMBERS | | | CORRESPONDING TO THE FLOOR PLAN. NEC 408.4 | | | | | | 3) PROVIDE LIGHTING CONTROL AS REQUIRED BY FBC 505.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|