| Plan Review Notes For Permit 15020001 |
| Permit Number |
15020001 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-24 16:24:54 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NOA THAT WAS SUBMITTED FOR THE SINGLE HUNG | | | WINDOWS HAS BEEN SUPERSEDED. THE CURRENT ONE IS NOA NO. | | | 14-0908.09. | | | | | | 2) IT APPEARS THAT SOME OF THE WINDOWS ARE DOUBLES THAT | | | ARE CONNECTED WITH A STRUCTURAL MULLION. PLEASE | | | CLARIFY. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL MULLIONS. MARK THE SIZES AND PRESSURES ON | | | THE PRODUCT APPROVAL FOR THE ONES THAT WILL BE USED. | | | FBC 107.3.4 & DCA RULE 9N-3 | | | | | | 3) SPECIFY THE DESIGN PRESSURE AND THE GLASS TYPE FOR | | | THE WINDOWS BY MARKING THEM ON THE PRODUCT APPROVALS. | | | FBC 107.3.4 | | | | | | |
|