| Plan Review Notes For Permit 15011082 |
| Permit Number |
15011082 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-16 15:29:16 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THE STRUCTURAL WINDOW MULLIONS. DCA RULE 9N-3 | | | | | | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | STORM PANELS AND THE 9 X 7 SECTIONAL GARAGE DOOR HAVE | | | INSTALLATION DRAWINGS THAT ARE MISSING INFORMATION. THE | | | DRAWINGS WERE NOT SHRUNK TO FIT ON THE 8.5" X 11" SIZE | | | PAPER AND ARE MISSING REQUIRED INFORMATION. | | | | | | 3) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN | | | INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM | | | PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, | | | TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL | | | LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO | | | GLASS AND THE APPLICABLE SECTION NUMBER FROM THE | | | INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE | | | CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF | | | THE RELATED FORMS INCLUDING | | | THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | | DEVICES. | | | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ | | | | | | 4) SPECIFY THE SPACING OF THE #14 WOOD SCREW ANCHORS. | | | | | | | | | | | | | | | |
|