| 2015-02-24 08:52:56 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT |
| | APPROVALS FOR THE NEW SINGLE HUNG WINDOWS AND |
| | STRUCTURAL MULLIONS. |
| | |
| | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | STORM PANELS AND THE 9 X 7 SECTIONAL GARAGE DOOR HAVE |
| | INSTALLATION DRAWINGS THAT ARE MISSING INFORMATION. IT |
| | APPEARS THAT THE DRAWINGS WERE NOT SHRUNK TO FIT ON THE |
| | 8.5" X 11" SIZE PAPER. |
| | |
| | 3) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN |
| | INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| | PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, |
| | TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL |
| | LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO |
| | GLASS AND THE APPLICABLE SECTION NUMBER FROM THE |
| | INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE |
| | CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF |
| | THE RELATED FORMS INCLUDING |
| | THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES. |
| | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| | |
| | 4) SHOW THAT THE EGRESS DOOR REQUIRED BY FBC - R311.1 |
| | WILL REMAIN IN COMPLIANCE WITH FBC- R311.2 AND BE |
| | READILY OPENABLE FROM INSIDE THE DWELLING WITHOUT THE |
| | USE OF A SPECIAL KEY OR SPECIAL KNOWLEDGE OR EFFORT |
| | WHEN THE STORM PANELS ARE IN PLACE. |
| | |
| | |
| | |