Plan Review Notes
Plan Review Notes For Permit 15011065
Permit Number 15011065
Review Stop B
Sequence Number 2
Notes
Date Text
2015-02-11 13:17:051) THE SHEET THAT WAS SUBMITTED FOR THE UL WALL
 ASSEMBLIES IS ILLEGIBLE. THE PRINTING IS TOO SMALL TOO
 READ. SUBMIT LEGIBLE COPIES. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1. 2ND REQUEST.
 2) SUBMIT 2 COPIES OF ALL PLAN SHEETS. WPB AMEND. TO
 2010 FBC SEC. 107.2.1. 2ND REQUEST.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE QUIETCORK PRODUCT. THE PRODUCT
 SHALL MEET THE TEST STANDARS LISTED IN THE 2010 FBC-B
 SEC.1207.3, 703.4, 703.4.1, 703.4.2. 2ND REQUEST.
 4)THERE IS AN 8 1/2" X 11" SHEET THAT HAS BEEN
 SUBMITTED THAT HAS 2 DIFFERENT UL JOINT SYSTEMS ON IT
 FOR RATED WALLS AND THE PLANS HAVE A WALL DETAIL AND A
 REFERENCE TO UL DESIGN # 419. IF THE DETAILS FROM THE 8
 1/2" X 11" SHEETS ARE NOT GOING TO BE USED, REMOVE
 THESE DETAILS FROM THE PERMIT PACKAGE. IF THEY ARE TO
 BE USED, SUBMIT 2 COPIES OF ALL APPLICABLE PAGES.
 5) THE PLAN REFERS TO UL DESIGN #419. SUBMIT THE DETAIL
 FROM THE UL BOOK FOR THIS ASSEMBLY.
 6) THE 8 1/2 " SHEETS REFER TO "QUIETCORK" UNDERLAYMENT
 BUT A TEST REPORT FOR "PROTECTOWRAP WHISPERCOAT
 UNDERLAYMENT" HAS BEEN SUBMITTED. WHICH IS BEING USED?
 THE UNDERLAYMENT SHALL COMPLY WITH THE 2010 FBC SECS.
 1207.3, 703.4, 703.4.1, 703.4.2. SHOW COMPLIANCE.
  
 PUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  