| Date |
Text |
| 2015-02-11 13:17:05 | 1) THE SHEET THAT WAS SUBMITTED FOR THE UL WALL |
| | ASSEMBLIES IS ILLEGIBLE. THE PRINTING IS TOO SMALL TOO |
| | READ. SUBMIT LEGIBLE COPIES. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. 2ND REQUEST. |
| | 2) SUBMIT 2 COPIES OF ALL PLAN SHEETS. WPB AMEND. TO |
| | 2010 FBC SEC. 107.2.1. 2ND REQUEST. |
| | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE QUIETCORK PRODUCT. THE PRODUCT |
| | SHALL MEET THE TEST STANDARS LISTED IN THE 2010 FBC-B |
| | SEC.1207.3, 703.4, 703.4.1, 703.4.2. 2ND REQUEST. |
| | 4)THERE IS AN 8 1/2" X 11" SHEET THAT HAS BEEN |
| | SUBMITTED THAT HAS 2 DIFFERENT UL JOINT SYSTEMS ON IT |
| | FOR RATED WALLS AND THE PLANS HAVE A WALL DETAIL AND A |
| | REFERENCE TO UL DESIGN # 419. IF THE DETAILS FROM THE 8 |
| | 1/2" X 11" SHEETS ARE NOT GOING TO BE USED, REMOVE |
| | THESE DETAILS FROM THE PERMIT PACKAGE. IF THEY ARE TO |
| | BE USED, SUBMIT 2 COPIES OF ALL APPLICABLE PAGES. |
| | 5) THE PLAN REFERS TO UL DESIGN #419. SUBMIT THE DETAIL |
| | FROM THE UL BOOK FOR THIS ASSEMBLY. |
| | 6) THE 8 1/2 " SHEETS REFER TO "QUIETCORK" UNDERLAYMENT |
| | BUT A TEST REPORT FOR "PROTECTOWRAP WHISPERCOAT |
| | UNDERLAYMENT" HAS BEEN SUBMITTED. WHICH IS BEING USED? |
| | THE UNDERLAYMENT SHALL COMPLY WITH THE 2010 FBC SECS. |
| | 1207.3, 703.4, 703.4.1, 703.4.2. SHOW COMPLIANCE. |
| | |