| 2015-03-06 12:55:20 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND THE DESIGN PROFESSIONAL FEES. VALUATION WAS |
| | UPDATED TO $56,793 FOR THE ADDITION ALONE. NEED TO ADD |
| | THE VALUE FOR ALL THE SCOPE OF WORK SHOWN ON SHEET A-2. |
| | |
| | 3- SHEET A-1: |
| | A) NEW FIRST FLOOR PLAN IS MISSING ALL DIMENSIONS. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | B) ROOF PLAN IS MISSING THE ROOF PITCH. SEC. R905.2.2 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE ROOF VENTILATION AS REQUIRED BY SEC. R806 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 6- SHEET S-3: |
| | A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE |
| | "C" NOT "B". REVISE AS REQUIRED. AND REVISE ALL THE |
| | COMPONENTS AND CLADDING WIND DESIGN PRESSURES |
| | ACCORDINGLY. |
| | |
| | B) REVISE THE ROOF LIVE LOAD (ATTIC LIVE LOAD) TO |
| | COMPLY WITH TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) REVISE NOTE #1 OF COMPONENTS & CLADDING WIND |
| | PRESSURES. ACCORDING TO FOOTNOTE ON FIGURE R301.2(7) OF |
| | 2010 FBC-RESIDENTIAL. THE MIN. DIMENSION "A" IS 4'-0" |
| | NOT "3'-0". REVISE AS REQUIRED. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) NEW BATHROOM SINGLE HUNG WINDOW. |
| | |
| | B) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING |
| | DON'T HAVE IMPACT GLASS. AND PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. |
| | |
| | C) ROOF SHINGLES. |
| | |
| | D) METAL DOME VENTS AS SPECIFIED ON NOTE #1 ON SHEET |
| | A-2. |
| | |
| | E) SELF ADHERING MODIFIED UNDERLAYMENT SPECIFIED ON |
| | NOTE #1 ON SHEET A-2. |
| | |
| | F) EXTERIOR DOORS TO BE REPLACED AS SPECIFIED ON NOTE |
| | #10 ON SHEET A-2. |
| | |
| | G) ALL WINDOWS TO BE REPLACED AS SPECIFIED ON NOTE#11 |
| | ON SHEET A-2. |
| | |
| | H) WINDOW MULLIONS, IF WINDOWS ARE MULLED TOGETHER. |
| | |
| | I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS, DETAILS AND NOTES. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR. OR LIST FLORIDA PRODUCT APPROVAL |
| | NUMBER (2010 FBC VERSION) NEXT TO THE SPECIFIED |
| | CONNECTOR. |
| | |
| | J) PRE-CAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- PROVIDE SKETCH SHOWING ALL WINDOWS TO BE REPLACED. |
| | SPECIFY EXISTING TYPE AND SIZE OF WINDOWS AND TYPE AND |
| | SIZE OF PROPOSED ONES TO VERIFY COMPLIANCE WITH THE |
| | BEDROOM EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| | FBC-EXISTING BUILDING. CLEARLY IDENTIFY ALL ROOMS, |
| | SPECIALLY ALL BEDROOMS. |
| | |
| | 10- DETAIL 2/S-2: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING HOW THE EXISTING TRUSSES THAT |
| | WILL BE CUT, WILL BE REINFORCED TO BE STRUCTURALLY |
| | SOUND. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 11- SHEET S-1: REVISE NOTE #6.2: SEC. R803.2.3.1 OF |
| | 2010 FBC-RESIDENTIAL REQUIRES 8D- RING SHANK NAILS. |
| | CLEARLY SPECIFY RING SHANK NAILS FOR THE ROOF |
| | SHEATHING. |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET. |
| | SUBMITT OLD DRAWING FOR QUICK REFERENCE. |
| | |