| | PROJECT: ADDITION 320 VALENCIA |
| | PERMIT#: 15011059 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A PANEL SCHEDULE INDICATING EXISTING |
| | CIRCUITS AND NEW CIRCUITS REQUIRED FOR ADDITION. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. WPB |
| | AMENDMENTS TO FBC 107 |
| | |
| | 3) PROVIDE AND INDICATE ON THE FLOOR PLAN SMOKE |
| | DETECTORS AS REQUIRED BY THE FBC-R 314 AND 315 AS |
| | APPLICABLE. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 4) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| | THE ELECTRICAL PANEL ON THE FLOOR PLAN. WPB AMENDMENTS |
| | TO FBC 107 |
| | |
| | 5) ADD RECEPTACLES ALONG WALL LINE OF NEW ADDITION AS |
| | REQUIRED BY THE NEC 210.52. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| | M (6 FT) FROM A RECEPTACLE OUTLET. |
| | |
| | 6) REVISE THE ELECTRICAL RISER DIGRAM TO INDICATE THE |
| | SIZE OF THE PROPOSED OCPD FFEEDING NEW A/C |
| | |
| | 7) PROVIDE A SWITCHED LIGHT OUTLET IN THE BEDROOM. NEC |
| | 210.70.210.70(1) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |