2015-01-30 11:33:44PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUE FOR THE WORK IS LOW. THE CALCULATED VALUE
 IS $15,912.00. THE VALUE HAS BEEN ADJUSTED. FBC 109.3
  
 2) THE MAXIMUM DESIGN PRESSURE FOR THE GAF MODIFIED
 ROOF SYSTEM IS NOT ADEQUATE FOR THE PERIMETER AND
 CORNER ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING IN THESE
 AREAS AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE 29 OF
 THE NOA NO. 14-0611.01. FBC R301.2.1
  
 3) ACCORDING TO NOA NO. 11-0321.03 THE ATTACHMENT
 RESISTANCE USING ONE #8 SCREW PROVIDES 20.7 FT LBS. OF
 ATTACHMENT RESISTANCE. THIS IS NOT ADEQUATE FOR THIS
 STRUCTURE. FBC R301.2.1