| Permit Number |
15011048 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-28 08:07:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. NEW COMMENT | | | : SPECIFY THE OVERCURRENT PROTECTION AND WIRE SIZES FOR | | | EACH CIRCUIT IN THE PANEL SCHEDULE. | | | | | | 2) AS SHOWN ON THE RISER DIAGRAM, THE #1CU FEEDER WIRES | | | TO THE 150 AMP PANEL ARE UNDERSIZED. WHEN THERE IS MORE | | | THAN ONE PANEL FEEDERS ARE REQUIRED TO BE SIZED IN | | | ACCORDANCE WITH NEC TABLE 310.16. THE SMALLEST SIZE | | | FEEDERS FOR A 150 AMP PANEL IN THIS DESIGN ARE 1/0 CU. | | | | | | 3) THE PANEL SCHEDULE ON SHEET A.11 FOR PANEL 'A' IS | | | INCORRECTLY LABELED AS 100 AMP. IT SHOULD BE 150 AMP | | | ACCORDING TO THE RISER DIAGRAM. FBC 107.2.1 | | | | | | 4) SERVICE DISCONNECT IS REQUIRED FOR NEW A/C | | | CONDENSING UNIT AT GYM. NEC 440.11 | | | |
|