| 2015-05-28 16:39:55 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION |
| | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER |
| | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS |
| | 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2 |
| | CODE COMPLIANCE CERTIFICATION. |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | |
| | 2 THE ELEVATIONS ON SHEETS A.09 INDICATES THAT THE |
| | DOORS AND WINDOWS IN THE ENTRY FOYER ARE 9'-0" IN |
| | HEIGHT AND THE FLOOR PLAN ON A.04 CALLS OUT 8'-0" TALL |
| | WINDOWS AND DOORS. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 3) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN |
| | PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS |
| | WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN |
| | THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC |
| | 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO |
| | BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH |
| | THE 8' TALL WINDOWS IN THE NEW ENTRY FOYER. |
| | |
| | 4) THE CORRECTED RAS 117 CALCULATIONS FOR THE BUILT UP |
| | ROOFING ARE REQUIRED TO HAVE THE ENGINEER'S SEAL AND |
| | ORIGINAL HANDWRITTEN SIGNATURE. COPIES AND OTHER |
| | FACSIMILES ARE NOT ACCEPTABLE. FS 471 |
| | |
| | |