2015-05-28 16:39:55PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2
 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2 THE ELEVATIONS ON SHEETS A.09 INDICATES THAT THE
 DOORS AND WINDOWS IN THE ENTRY FOYER ARE 9'-0" IN
 HEIGHT AND THE FLOOR PLAN ON A.04 CALLS OUT 8'-0" TALL
 WINDOWS AND DOORS. PLEASE CLARIFY. FBC 107.2.1
  
 3) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN
 PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS
 WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN
 THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC
 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO
 BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH
 THE 8' TALL WINDOWS IN THE NEW ENTRY FOYER.
  
 4) THE CORRECTED RAS 117 CALCULATIONS FOR THE BUILT UP
 ROOFING ARE REQUIRED TO HAVE THE ENGINEER'S SEAL AND
 ORIGINAL HANDWRITTEN SIGNATURE. COPIES AND OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FS 471
  
  