2015-02-05 05:20:211) THE PLANS SHALL BE SIGNED AND SEALED BY THE
 ARCHITECT PER THE FL. ADMIN. CODE RULE 61G1-16.001.
 2) SUBMIT MANUF. SPECS/INSTALLATION MANUAL FOR ALL GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER
 THE FBCR SEC. G2404.3.
 3) IDENTIFY ALL THE BATHS ON THE FLOOR PLAN SHT.A.04.
 THE NAMES OF THE BATHS ON THE FLOOR PLAN DO NOT MATCH
 THE NAMES ON THE PLBG. RISER. CLARIFY. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4)THE PREP SINK IN THE KITCHEN IS NOT SHOWN ON THE
 KITCHEN SANITARY RISER. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN ALL STACKS PER 2010 FBCR
 SEC.P3005.2.6.
 6) SUBMIT A WATER RISER DIAGRAM FOR NEW BATHS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 7) IDENTIFY THE PIECE OF EQUIPMENT MARKED "WP" IN THE
 UTILITY ROOM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW