| Permit Number |
15011048 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-05 05:20:21 | 1) THE PLANS SHALL BE SIGNED AND SEALED BY THE | | | ARCHITECT PER THE FL. ADMIN. CODE RULE 61G1-16.001. | | | 2) SUBMIT MANUF. SPECS/INSTALLATION MANUAL FOR ALL GAS | | | APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER | | | THE FBCR SEC. G2404.3. | | | 3) IDENTIFY ALL THE BATHS ON THE FLOOR PLAN SHT.A.04. | | | THE NAMES OF THE BATHS ON THE FLOOR PLAN DO NOT MATCH | | | THE NAMES ON THE PLBG. RISER. CLARIFY. WPB AMEND. TO | | | 2010 FBC SEC. 107.2.1. | | | 4)THE PREP SINK IN THE KITCHEN IS NOT SHOWN ON THE | | | KITCHEN SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 5) CLEANOUTS ARE REQUIRED IN ALL STACKS PER 2010 FBCR | | | SEC.P3005.2.6. | | | 6) SUBMIT A WATER RISER DIAGRAM FOR NEW BATHS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 7) IDENTIFY THE PIECE OF EQUIPMENT MARKED "WP" IN THE | | | UTILITY ROOM.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|