| Plan Review Notes For Permit 15011048 |
| Permit Number |
15011048 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-12 15:19:50 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | | | 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. | | | | | | 3) NEC 240.24(A) & (B) PANELS SHALL BE READILY | | | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. | | | SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL | | | FLOOR PLAN. | | | | | | 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. THE | | | RECEPTICALS FOR THE GARAGE DOOR OPENERS SHALL BE GFCI | | | PROTECTED. | | | | | | 5) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL | | | BE PROVIDED. | | | | | | 6) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE | | | BONDED. | | | | | | 7) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLETS. | | | | | | 8) LUMINAIRES IN CLOTHES CLOSETS SHALL OF THE TYPE | | | PERMITTED AND LOCATED AS REQUIRED BY NEC 410.16 (A) - | | | (C) . | | | | | | | | | | | | | | | | | | |
|