Plan Review Notes
Plan Review Notes For Permit 15011048
Permit Number 15011048
Review Stop E
Sequence Number 1
Notes
Date Text
2015-03-12 15:19:50PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 3) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL
 FLOOR PLAN.
  
 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. THE
 RECEPTICALS FOR THE GARAGE DOOR OPENERS SHALL BE GFCI
 PROTECTED.
  
 5) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 6) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 7) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 8) LUMINAIRES IN CLOTHES CLOSETS SHALL OF THE TYPE
 PERMITTED AND LOCATED AS REQUIRED BY NEC 410.16 (A) -
 (C) .
  
  
  
  
  
  