2015-03-12 07:59:32PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A.02 THE NOTES FOR THE BRICK BBQ HAVE BEEN
 PRINTED OVER AND ARE ILLEGIBLE. PLEASE CORRECT. FBC
 107.2.1
  
 2) ON SHEET A.12 THE STRUCTURAL CRITERIA CONTAINS
 MISTAKES. THE PROJECT IS LOCATED IN A WINDBORNE DEBRIS
 REGION AND THE RISK CATEGORY ( WIND IMPORTANCE FACTOR )
 SHOULD BE II. FBC 1609.2 & 1604.5
  
 3) THE WINDOW AND DOOR BUCK DETAILS ON SHEET A1.2 DO
 NOT SPECIFY THE ANCHOR SPACING FOR THE TAPCONS. FBC
 107.2.1
  
 4) ON SHEET 6 OF THE STRUCTURAL DRAWINGS THE EXPOSURE
 CATEGORY IS INCORRECTLY SPECIFIED AS "C". THE PROJECT
 IS LOCATED WITHIN 600 FEET OF THE INTERCOASTAL WATER
 WAY AND IS EXPOSURE "D". PLEASE CHECK TO SEE THAT ALL
 COMPONENT AND CLADDING PRESSURES ON THE PLANS ARE FOR
 EXPOSURE "D".
  
 5) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2
 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 6) ON SHEET 1 OF THE STRUCTURAL DRAWINGS SOME OF THE C4
 COLUMNS ARE NOT MARKED AT THE COVERED LOGGIA. FBC
 107.2.1
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT
 APPROVALS FOR THE ASPHALT SHINGLE OR METAL ROOFING,
 HORIZONTAL ROLLING WINDOWS AND THE STRUCTURAL MULLIONS.
  
 8) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN
 PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS
 WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN
 THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC
 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO
 BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH
 THE 8' TALL WINDOWS IN THE NEW FOYER.
  
 9) THE RAS 117 CALCULATIONS FOR THE BUILT UP ROOFING
 MATERIAL SPECIFY THE FASTENER SPACING FOR THE CORNER
 AREAS AS 3.4" O.C. RAS 117 SECTION 8.1 SPECIFIES THAT
 THE MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN
 4 IN. O.C. PLEASE REVISE THE CALCULATIONS.
  
 10) ASPHALT SHINGLES ARE SPECIFIED TO BE INSTALLED ON
 THE GARAGE ON SHEET A.01 AND THE ELEVATIONS SHOW A NEW
 METAL ROOF. CLARIFY. FBC 107.2.1
  
  