| 2015-03-12 07:59:32 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ON SHEET A.02 THE NOTES FOR THE BRICK BBQ HAVE BEEN |
| | PRINTED OVER AND ARE ILLEGIBLE. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 2) ON SHEET A.12 THE STRUCTURAL CRITERIA CONTAINS |
| | MISTAKES. THE PROJECT IS LOCATED IN A WINDBORNE DEBRIS |
| | REGION AND THE RISK CATEGORY ( WIND IMPORTANCE FACTOR ) |
| | SHOULD BE II. FBC 1609.2 & 1604.5 |
| | |
| | 3) THE WINDOW AND DOOR BUCK DETAILS ON SHEET A1.2 DO |
| | NOT SPECIFY THE ANCHOR SPACING FOR THE TAPCONS. FBC |
| | 107.2.1 |
| | |
| | 4) ON SHEET 6 OF THE STRUCTURAL DRAWINGS THE EXPOSURE |
| | CATEGORY IS INCORRECTLY SPECIFIED AS "C". THE PROJECT |
| | IS LOCATED WITHIN 600 FEET OF THE INTERCOASTAL WATER |
| | WAY AND IS EXPOSURE "D". PLEASE CHECK TO SEE THAT ALL |
| | COMPONENT AND CLADDING PRESSURES ON THE PLANS ARE FOR |
| | EXPOSURE "D". |
| | |
| | 5) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION |
| | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER |
| | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS |
| | 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2 |
| | CODE COMPLIANCE CERTIFICATION. |
| | THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | |
| | 6) ON SHEET 1 OF THE STRUCTURAL DRAWINGS SOME OF THE C4 |
| | COLUMNS ARE NOT MARKED AT THE COVERED LOGGIA. FBC |
| | 107.2.1 |
| | |
| | 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT |
| | APPROVALS FOR THE ASPHALT SHINGLE OR METAL ROOFING, |
| | HORIZONTAL ROLLING WINDOWS AND THE STRUCTURAL MULLIONS. |
| | |
| | 8) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN |
| | PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS |
| | WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN |
| | THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC |
| | 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO |
| | BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH |
| | THE 8' TALL WINDOWS IN THE NEW FOYER. |
| | |
| | 9) THE RAS 117 CALCULATIONS FOR THE BUILT UP ROOFING |
| | MATERIAL SPECIFY THE FASTENER SPACING FOR THE CORNER |
| | AREAS AS 3.4" O.C. RAS 117 SECTION 8.1 SPECIFIES THAT |
| | THE MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN |
| | 4 IN. O.C. PLEASE REVISE THE CALCULATIONS. |
| | |
| | 10) ASPHALT SHINGLES ARE SPECIFIED TO BE INSTALLED ON |
| | THE GARAGE ON SHEET A.01 AND THE ELEVATIONS SHOW A NEW |
| | METAL ROOF. CLARIFY. FBC 107.2.1 |
| | |
| | |