2015-04-26 13:13:20BUILDING PLAN REVIEW
 PERMIT: 15011018
 ADD: 2020 PALM BEACH LAKES
 CONT: TBD
 TEL: (770)799-2273
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. APRIL 26/ 2015
 ACTION: BUILDING PROVISO
  
 1) SUBMITTED GAF ROOFING REPORT FL 16730-R4 GAF
 EVERGUARD EXTREME TPO SINGLE PLY ROOFING SYSTEM WAS
 SUBMITTED WITH THE 68-PAGE APPENDIX. THE 68 PAGE
 APPENDIX LIST ALL SUB-SYSTEMS, ATTACHMENTS AS WELL AS
 MAXIMUM DESIGN PRESSURES AND LIMITATIONS SEE APPENDIX
 SHEET #2. THE APPENDIX 68 PAGES OF SUB-SYSTEMS WERE
 REVIEWED, NO SUB-SYSTEM WAS IDENTIFIED.
  
 THE ROOFING CONTRACTOR UNDER THE SUB-PERMIT WILL BE
 REQUIRED TO SUBMIT THE PRODUCT APPROVAL APPROVED BY THE
 DESIGNER OF RECORD WITH SHOP DRAWING STAMP OF APPROVAL
 AND THE SUB-SYSTEM IDENTIFIED WITH ASSOCIATED
 PRESSURES, DEPENDING ON THE TYPE OF FASTENING SYSTEM
 ELECTED, MAY OR MAY NO REQUIRE ENHANCED FASTENING SEE
 APPENDIX SHEET # 2 FOR NOTES AND LIMITATIONS OF THE
 PRODUCT.
  
 PLAN REVIEW FEES WILL BE ASSOCIATED THE SUB-ROOFING
 PERMIT FOR REVIEW OF SUB-SYSTEM IDENTIFICATION.
  
 2) 107. 3.4.2 DEFERRED SUBMITTALS :
 1) PREMADE RAIN SCREEN SYSTEMS
 2) FUTURE CANOPY
 THESE DEFERRED SUBMITTALS WILL NEED TO MEET THE WIND
 DESIGN REQUIREMENTS AND BE REVIEWED BY THE DESIGNER OF
 RECORD BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 .
  
  