| 2015-04-26 13:13:20 | BUILDING PLAN REVIEW |
| | PERMIT: 15011018 |
| | ADD: 2020 PALM BEACH LAKES |
| | CONT: TBD |
| | TEL: (770)799-2273 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: SUN. APRIL 26/ 2015 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SUBMITTED GAF ROOFING REPORT FL 16730-R4 GAF |
| | EVERGUARD EXTREME TPO SINGLE PLY ROOFING SYSTEM WAS |
| | SUBMITTED WITH THE 68-PAGE APPENDIX. THE 68 PAGE |
| | APPENDIX LIST ALL SUB-SYSTEMS, ATTACHMENTS AS WELL AS |
| | MAXIMUM DESIGN PRESSURES AND LIMITATIONS SEE APPENDIX |
| | SHEET #2. THE APPENDIX 68 PAGES OF SUB-SYSTEMS WERE |
| | REVIEWED, NO SUB-SYSTEM WAS IDENTIFIED. |
| | |
| | THE ROOFING CONTRACTOR UNDER THE SUB-PERMIT WILL BE |
| | REQUIRED TO SUBMIT THE PRODUCT APPROVAL APPROVED BY THE |
| | DESIGNER OF RECORD WITH SHOP DRAWING STAMP OF APPROVAL |
| | AND THE SUB-SYSTEM IDENTIFIED WITH ASSOCIATED |
| | PRESSURES, DEPENDING ON THE TYPE OF FASTENING SYSTEM |
| | ELECTED, MAY OR MAY NO REQUIRE ENHANCED FASTENING SEE |
| | APPENDIX SHEET # 2 FOR NOTES AND LIMITATIONS OF THE |
| | PRODUCT. |
| | |
| | PLAN REVIEW FEES WILL BE ASSOCIATED THE SUB-ROOFING |
| | PERMIT FOR REVIEW OF SUB-SYSTEM IDENTIFICATION. |
| | |
| | 2) 107. 3.4.2 DEFERRED SUBMITTALS : |
| | 1) PREMADE RAIN SCREEN SYSTEMS |
| | 2) FUTURE CANOPY |
| | THESE DEFERRED SUBMITTALS WILL NEED TO MEET THE WIND |
| | DESIGN REQUIREMENTS AND BE REVIEWED BY THE DESIGNER OF |
| | RECORD BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |