Plan Review Notes
Plan Review Notes For Permit 15011018
Permit Number 15011018
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-31 06:14:20!) PROVIDE A WATER AND SANITARY RISER ON THE PLANS PER
 WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) PROVIDE ROOF DRAINAGE DETAILS / CALCULATIONS,
 SCUPPER DETAILS, ETC. COMPLY WITH 2010 FBC SEC.1503.4
 AND CHAPTER 11 OF THE 2010 FL. PLBG. CODE AND WPB
 AMEND. TO 2010 FBC SEC. 107.2.1, FBC 1503.4 THRU
 1503.4.2.1.
 3) ONE HALF OF THE AREA OF THE MODIFIED PARAPET WALL
 SHALL BE ADDED TO THE ROOF DRAINAGE CALCULATIONS PER
 2010 FPC SEC.1106.4.
 4) SHT. A 210 REFERS TO A NEW SCUPPER. PROVIDE A
 SCUPPER DETAIL SHOWING L X W . SCUPPER SHALL COMPLY W/
 2010 FPC TABLE 1106.7.
 5) SECONDARY DRAINAGE IS REQUIRED FOR THE ROOF SYSTEM
 PER SEC.1107.1 OF THE 2010 FPC AND 1503.4.1 OF THE 2010
 FBC. SUPPLY DETAILS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  