| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED: |
| | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | |
| | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 4) IS THERE AN ACTIVE FIRE ALARM SYSTEM AT THIS |
| | LOCATION? IF SO, PLEASE PROVIDE DETAILS REGARDING |
| | LOCATION OF FACP. |
| | |
| | 5) FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF |
| | 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA |
| | BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON |
| | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE |
| | MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED |
| | DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN |
| | STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING |
| | IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| | SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | |