| Plan Review Notes For Permit 15010983 |
| Permit Number |
15010983 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-02-28 10:51:28 | 1) SHT.CS-1 & LS-1 BOTH INDICATE THIS OCCUPANCY AS A | | | BUSINESS OCCUPANCY BUT THE PLAN CLEARLY STATES THIS AS | | | A RETAIL SPACE AND HAS A DINING AREA. DEPENDING ON THE | | | OCCUPANT LOAD, IT COULD BE ASSEMBLY, OR MERCANTILE PER | | | SEC.303. CLARIFY.2ND REQUEST. | | | 2) SUBMIT THE SQUARE FOOTAGE OF THIS SPACE.WPB | | | AMENDMENTS TO 2010 FBC SEC.107.2.1. 2ND REQUEST. | | | 3) SUBMIT THE OCCUPANT LOAD OF THIS SPACE..WPB | | | AMENDMENTS TO 2010 FBC SEC.107.2.1.2ND REQUEST. | | | 4) INDICATE ON THE PLANS THE TYPE OF FOODS THAT WILL BE | | | PREPARED AND SOLD. WPB AMENDMENTS TO 2010 FBC | | | SEC.107.2.1.2ND REQUEST. | | | 5) SUBMIT THE SIZING CALCULATIONS THAT WERE USED TO | | | SIZE THE SCHIER GREASE INTERCEPTOR.2010 FPC SEC.1003.2. | | | 6) THE GREASE INTERCEPTOR SHALL BE VENTED IN ACCORDANCE | | | THE 2010 FPC SEC.1003.3.4.2. | | | 7) THE REVISED SHEETS SHALL BE INSERTED INTO THE MASTER | | | SET BY THE APPLICANT. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|