Plan Review Notes
Plan Review Notes For Permit 15010983
Permit Number 15010983
Review Stop B
Sequence Number 2
Notes
Date Text
2015-02-27 06:09:55BUILDING PLAN REVIEW
 PERMIT: 15010983
 ADD: 401 S. DIXIE HWY. SUITE # 3
 CONT: T. B. D.
 TEL: (561)389-3887
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 27/2015
 ACTION: DENIED
  
 NOTE!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1) 2ND REQUEST. BOTH THE COVER SHEET INDICATE THIS TO
 BE A BUSINESS OCCUPANCY, THE PLANS INDICATE A COFFEE
 SHOP. THIS SPACE APPEARS TO BE AN A-2 OCCUPANCY
 INTENDED FOR FOOD AND/OR DRINK CONSUMPTION, NOTE THE
 OCCUPANT LOAD WOULD NEED TO BE 50 OR MORE OCCUPANTS.
 FBC-B 303.1 ALSO SEE 309.1 MERCANTILE RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS
 THAN 50 PERSONS.
  
 2)COMPLIED. THE LIFE SAFETY SHEET INDICATES THE SQUARE
 FOOTAGE FOR THE 1ST FLOOR, BUT NOT FOR THIS TENANT
 SPACE, PLEASE PROVIDE THE SQUARE FOOTAGE AND OCCUPANT
 LOAD PER FBC-B TABLE 1004.1.1 FOR THIS TENANT SPACE.
  
 3) 2ND REQUEST. RESPONCE THE DESIGNER OF RECORD QOUTED
 THE CODE SECTION FOR COMPLIANCE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART.
  
 THE LIFE SAFETY PLAN DOES NOT SHOW TABLES AND CHAIRS IN
 THE DINING AREA NOR COMPLIANCE WITH AISLE ACCESS WAY
 FOR TABLES & CHAIRS, 2010 FBC-B 1017.4 (1)-(3) NOR
 1028.9.1 AND 1028.9.1.1.
  
 4) PROVISO: WILL BE INSPECTED IN THE FIELD FOR CODE
 COMPLIANCE FOR THE FLORIDA ACCESSIBILITY CODE. ISHEET
 A-1.0 SHOWS 2 PIECES OF MILLWORK SUPPLIED BY OWNER, WE
 DO NOT KNOW THE USAGE AND IF THESE UNITS COMPLY WITH
 THE 2010 FBC- ACCESSIBILITY CODE 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES.
  
 5) 2ND REQUEST. RESPONCE THE DESIGNER OF RECORD QOUTED
 THE CODE SECTION FOR COMPLIANCE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART.
  
 LIFE SAFETY NOR SHEET A-1.0 SHOW COMPLIANCE WITH 2010
 FL ACCESSIBILTY CODE 02.1 GENERAL. DINING SURFACES AND
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  