| 2015-01-31 08:27:20 | 1) SHT.CS-1 & LS-1 BOTH INDICATE THIS OCCUPANCY AS A |
| | BUSINESS OCCUPANCY BUT THE PLAN CLEARLY STATES THIS AS |
| | A RETAIL SPACE AND HAS A DINING AREA. DEPENDING ON THE |
| | OCCUPANT LOAD, IT COULD BE ASSEMBLY, OR MERCANTILE PER |
| | SEC.303. CLARIFY. |
| | 2) SUBMIT THE SQUARE FOOTAGE OF THIS SPACE.WPB |
| | AMENDMENTS TO 2010 FBC SEC.107.2.1. |
| | 3) SUBMIT THE OCCUPANT LOAD OF THIS SPACE..WPB |
| | AMENDMENTS TO 2010 FBC SEC.107.2.1. |
| | 4) INDICATE ON THE PLANS THE TYPE OF FOODS THAT WILL BE |
| | PREPARED AND SOLD. WPB AMENDMENTS TO 2010 FBC |
| | SEC.107.2.1. |
| | 5) THE PLUMBING PLANS INDICATE A SCHIER GREASE |
| | INTERCEPTOR. THE GREASE INTERCEPTOR SHALL BE |
| | DESIGNED/SIZED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTRUCTIONS. SUBMIT SIZING CALCULATIONS THAT HAVE BEEN |
| | DONE BY SCHIER TO ENSURE THE CORRECT SIZE IS BEING |
| | INSTALLED.2010 FPC SEC.1003.2. |
| | 6) SHT. P-2 SHOWS A DRY VENT ON THE SANITARY RISER |
| | DOWNSTREAM OF THE FLOOR DRAIN NEAR THE INLET OF THE |
| | GREASE INTERCEPTOR. COMPLY W/2010 FPC SEC.905.3. |
| | 7) SUBMIT MANUF. SPECIFICATIONS FOR THE SCHIER GREASE |
| | INTERCEPTOR.WPB AMENDMENTS TO 2010 FBC SEC.107.2.1. |
| | 8) SHT. P-2 - SIZE ALL VENTS ON THE SANITARY RISER.WPB |
| | AMENDMENTS TO 2010 FBC SEC.107.2.1. |
| | 9) SHT. P-2 SHOWS AN ITEM MARKED AS "D/W." IS THIS A |
| | DISHWASHER? IF SO, IT SHALL DRAIN THROUGH THE |
| | INTERCEPTOR. 2010 FPC SEC.1003.3.1.SHOW THE DRAIN ON |
| | THE SANITARY RISER. |
| | 10) FLOOR SINKS NOT RECEIVING INDIRECT WASTE DISCHARGE |
| | SHALL HAVE TRAP PRIMERS PER 2010 FPC SEC.1002.4. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |