Plan Review Notes For Permit 15010983
Permit Number 15010983
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-01-30 12:04:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS OF THE BUILDING, THE FIRE ALARM
 AND/OR FIRE SPRINKLER, SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 COOKING OR WARMING IN THE KITCHEN SHALL NOT PRODICE ANY
 GREASE LADEN VAPORS OR A NFPA 96 COMPLIANT HOOD,
 EXHAUST AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMIT..
  