Plan Review Notes
Plan Review Notes For Permit 15010983
Permit Number 15010983
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-12 10:59:092/13/2015
 PROJECT:401 S. DIXIE HWY STE 3
 PERMIT#: 15010983
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE CORRECTIONS TO THE ELECTRICAL PLANS TO COMPLY
 WITH REVIEW COMMENTS BELOW:
  
 1) CLARIFY RISER DIAGRAM WHERE PANEL AC1 IS ALSO
 INDICATED AS "NEW PANEL "D" DISC." THE NOTES UNDER THE
 RISER DIAGRAM STATES "NO WORK PROPOSED ON RISER; SHOWN
 FOR INFORMATIONAL PURPOSES ONLY." IF THERE IS A NEW
 PANEL "D" INDICATE FEEDER AND PANEL AS NEW WORK,
 PROVIDE LOCATION OF NEW PANEL, A COMPLETE PANEL
 SCHEDULE AND LOAD CALCULATION FOR MDP.
  
 2) NEC 110.16 ARC FLASH PROTECTION.
 VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR THE
 PANEL BOARDS AND MAIN DISCONNECTING MEANS.
  
 3) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 4) WPB AMENDMENTS TO FBC 107.2.1
 PROVIDE A SYMBOL ON THE SYMBOLS LEGEND ON SHEET E-1 FOR
 A GFI OUTLET OR ADD A GFI DESIGNATION TO THE OUTLETS
 DESIGNATED AS A SQUARE SYMBOL WITH TWO HORIZONTAL LINES
 IN THE KITCHEN COUNTER TOPS AND SINKS WHERE REQUIRED.
  
 5) FBC-E 505.2
 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
  
 6) FBC ENERGY CONSERVATION 505.3
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS.
  
 7) PROVIDE A LIGHTING FIXTURE DETAIL WITH MANUFACTURER
 SUBMITTALS ON OWNER PROVIDED LED ROPE LIGHT.
  
 8) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. HOOD EXHAUST, FIRE ALARM,
 ACCESS CONTROL SYSTEM, SECURITY, CCTV, AUDIO/VIDEO,
 NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  