| 2015-02-12 10:59:09 | 2/13/2015 |
| | PROJECT:401 S. DIXIE HWY STE 3 |
| | PERMIT#: 15010983 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | PROVIDE CORRECTIONS TO THE ELECTRICAL PLANS TO COMPLY |
| | WITH REVIEW COMMENTS BELOW: |
| | |
| | 1) CLARIFY RISER DIAGRAM WHERE PANEL AC1 IS ALSO |
| | INDICATED AS "NEW PANEL "D" DISC." THE NOTES UNDER THE |
| | RISER DIAGRAM STATES "NO WORK PROPOSED ON RISER; SHOWN |
| | FOR INFORMATIONAL PURPOSES ONLY." IF THERE IS A NEW |
| | PANEL "D" INDICATE FEEDER AND PANEL AS NEW WORK, |
| | PROVIDE LOCATION OF NEW PANEL, A COMPLETE PANEL |
| | SCHEDULE AND LOAD CALCULATION FOR MDP. |
| | |
| | 2) NEC 110.16 ARC FLASH PROTECTION. |
| | VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR THE |
| | PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| | |
| | 3) NEC 110.9 |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. |
| | |
| | 4) WPB AMENDMENTS TO FBC 107.2.1 |
| | PROVIDE A SYMBOL ON THE SYMBOLS LEGEND ON SHEET E-1 FOR |
| | A GFI OUTLET OR ADD A GFI DESIGNATION TO THE OUTLETS |
| | DESIGNATED AS A SQUARE SYMBOL WITH TWO HORIZONTAL LINES |
| | IN THE KITCHEN COUNTER TOPS AND SINKS WHERE REQUIRED. |
| | |
| | 5) FBC-E 505.2 |
| | LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| | 505.2.4. |
| | |
| | 6) FBC ENERGY CONSERVATION 505.3 |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. |
| | |
| | 7) PROVIDE A LIGHTING FIXTURE DETAIL WITH MANUFACTURER |
| | SUBMITTALS ON OWNER PROVIDED LED ROPE LIGHT. |
| | |
| | 8) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR GENERATORS. HOOD EXHAUST, FIRE ALARM, |
| | ACCESS CONTROL SYSTEM, SECURITY, CCTV, AUDIO/VIDEO, |
| | NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |