 PROJECT: DOUBLETREE
 PERMIT#: 15010976
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FBC SECTION 907
 FIRE ALARM AND DETECTION SYSTEMS
 SEVERAL ELEMENTS REQUIRED IN SECTION 907 ARE MISSING IN
 THIS SUBMITTAL. PROVIDE ALL REQUIRED ELEMENTS. PROVIDE
 MANUFACTURER SUBMITTALS AND SHOP DRAWINGS IN COMPLIANCE
 WITH ALL OF THE REQUIREMENTS LISTED IN FBC SECTION 907.
  
 2) FBC, WPB AMENDMENTS 107.2.1
 THE PLANS ARE NOT SIGNED.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006
 FBC, WPB AMENDMENTS 107.2.1 PROVIDE THE NAME AND
 SIGNATURE ON THE PLANS OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  