| 2015-02-02 09:56:03 | 2/2/2015 |
| | PROJECT: DOUBLETREE |
| | PERMIT#: 15010976 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FBC SECTION 907 |
| | FIRE ALARM AND DETECTION SYSTEMS |
| | SEVERAL ELEMENTS REQUIRED IN SECTION 907 ARE MISSING IN |
| | THIS SUBMITTAL. PROVIDE ALL REQUIRED ELEMENTS. PROVIDE |
| | MANUFACTURER SUBMITTALS AND SHOP DRAWINGS IN COMPLIANCE |
| | WITH ALL OF THE REQUIREMENTS LISTED IN FBC SECTION 907. |
| | |
| | 2) FBC, WPB AMENDMENTS 107.2.1 |
| | THE PLANS ARE NOT SIGNED. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| | 668.001-668.006 |
| | FBC, WPB AMENDMENTS 107.2.1 PROVIDE THE NAME AND |
| | SIGNATURE ON THE PLANS OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |