| 2015-07-07 14:59:31 | 3RD REVIEW; FBC 2010 MECHANICAL | | | | | | 1) SHEET MP-1: REMOVE THE CUT AND PASTE AHU-1 MOUNTING | | | DETAIL SHOWING A GARAGE INSTALLATION AND INACCURATE | | | SUPPLY DUCT SIZE NOT RELEVENT TO THIS PROJECT. | | | 2) MP-1: THE CLOSETS SHOWN ON THE PLAN ARE DEFINED AS | | | PLENUMS IN ACCORDANCE WITH SECTION 202 AND MUST BE | | | ENCLOSED WITH NON-COMBUSTIBLE MATERIALS PER SECTION | | | 602.2. PLEASE INDICATE THE TYPE OF MATERIAL USED TO | | | FORM THE PLENUM, AND VERIFY THE LOUVERED CLOSET DOORS | | | ARE CONSTRUCTED OF METAL. | | | 3) MP-1: SHOW THE REQUIRED 4" MINIMUM CLEARANCE AROUND | | | ALL SIDES OF THE AIR HANDLERS- SECFTION 603.1.3. | | | 4) MP-1: VERIFY THAT THE LOUVERED DOORS ARE PROVIDING A | | | MINIMUM OF 27 SQUARE INCHES OF RETURN AIR OPENING FOR | | | PROPER AIR BALANCING- SECTION 601.4. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|