2015-07-07 14:59:313RD REVIEW; FBC 2010 MECHANICAL
  
 1) SHEET MP-1: REMOVE THE CUT AND PASTE AHU-1 MOUNTING
 DETAIL SHOWING A GARAGE INSTALLATION AND INACCURATE
 SUPPLY DUCT SIZE NOT RELEVENT TO THIS PROJECT.
 2) MP-1: THE CLOSETS SHOWN ON THE PLAN ARE DEFINED AS
 PLENUMS IN ACCORDANCE WITH SECTION 202 AND MUST BE
 ENCLOSED WITH NON-COMBUSTIBLE MATERIALS PER SECTION
 602.2. PLEASE INDICATE THE TYPE OF MATERIAL USED TO
 FORM THE PLENUM, AND VERIFY THE LOUVERED CLOSET DOORS
 ARE CONSTRUCTED OF METAL.
 3) MP-1: SHOW THE REQUIRED 4" MINIMUM CLEARANCE AROUND
 ALL SIDES OF THE AIR HANDLERS- SECFTION 603.1.3.
 4) MP-1: VERIFY THAT THE LOUVERED DOORS ARE PROVIDING A
 MINIMUM OF 27 SQUARE INCHES OF RETURN AIR OPENING FOR
 PROPER AIR BALANCING- SECTION 601.4.
  