Plan Review Notes
Plan Review Notes For Permit 15010952
Permit Number 15010952
Review Stop M
Sequence Number 1
Notes
Date Text
2015-03-10 09:31:15PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS PER SECTION 321.1
 LOAD CALCULATIONS 2010 FBC (M) OR 503.2.1
 CALCULATIONS OF HEATING AND COOLING. 2010
 FLORIDA ENERGY CODE.
 2) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS 2010 FLORIDA ENERGY CODE.
 3) SIZE FRESH AIR DUCT. PER SECTION 107 FBC 2010
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M)
  