| 2015-03-10 09:31:15 | PLAN DENIED | | | 1) PROVIDE ENERGY CALCULATIONS PER SECTION 321.1 | | | LOAD CALCULATIONS 2010 FBC (M) OR 503.2.1 | | | CALCULATIONS OF HEATING AND COOLING. 2010 | | | FLORIDA ENERGY CODE. | | | 2) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER | | | CONTROLS 2010 FLORIDA ENERGY CODE. | | | 3) SIZE FRESH AIR DUCT. PER SECTION 107 FBC 2010 | | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR | | | 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|