| 2015-02-09 15:05:24 | 2/9/2015 |
| | PROJECT: 804 S. DIXIE |
| | PERMIT#: 15010952 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE SYSTEM VOLTAGE AT ELECTRICAL SERVICE RISER |
| | AND LOAD CALCULATION. PANEL SCHEDULES ARE NOTED AS |
| | 120/208VOLT 3PHASE 4 WIRE, THE LOAD CALCULATION USES |
| | 230VOLT 1PHASE? PROVIDE CONSYSTANCY WITH SYSTEM VOLTAGE |
| | THROUGHOUT. WPB AMENDMENTS TO FBC 107.2 |
| | |
| | 2) ELECTRICAL RISER INDICATES 3,3/0 AND 10,#2 CU IN 2" |
| | RIDGED CONDUIT FEEDING A 100AMP ELECTRICAL PANEL. THIS |
| | APPEARS TO BE A POSSIBLE TYPO BUT MAKES NO SENSE AND |
| | NEEDS TO BE ADDRESSED. THE SAME IS NOTED FROM THE |
| | SECOND 100AMP DISCONNECT FEEDING THE OTHER ELECTRICAL |
| | PANEL. PROVIDE A REVISED RISER DIAGRAM WITH ACTUAL WIRE |
| | SIZES TYPE AND QUANTITY. NEC 215.2 , 215.5 5 |
| | |
| | 3) PROVIDE FOR EMERGENCY AND EXIT LIGHTING ON THE |
| | ELECTRICAL FLOOR PLAN WHERE REQUIRED BY NEC 700.16 |
| | CIRCUIT EMERGENCY AND EXIT LIGHTING ON THE ELECTRICAL |
| | FLOOR AND PROVIDE THE CIRCUIT NUMBER IN THE PANEL |
| | SCHEDULE FEEDING THE EMERGENCY EXIT LIGHTING. NEC |
| | 700.12 |
| | |
| | 4) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52 |
| | |
| | 5) PANEL A IS IDENTIFIED AS A 100AMP PANEL. THE LOAD |
| | CALCULATION INDICATES A 116AMP LOAD ON PANEL A. REVISE |
| | THE RISER AND PANEL OR THE LOAD. NEC 215.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |