| Plan Review Notes For Permit 15010921 |
| Permit Number |
15010921 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-29 13:20:52 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED REVISED | | | MECHANICAL PLAN SHEETS M-1A, M-1B, M-1C, M-1D AND M-1F. | | | THE APPROVED MECHANICAL PLANS WERE SIGNED AND SEALED BY | | | STEPHEN WALSH, P.E. | | | | | | 2) THE ENERGY CALCULATIONS FOR THE "MASTER" PLAN SHOULD | | | BE WORST CASE. THE ENERGY CALCULATIONS AND EQUIPMENT | | | SIZING CALCULATIONS FOR EACH OF THE SPECIFIC BUILDINGS | | | "BABIES" ARE REQUIRED TO BE SITE SPECIFIC BASED ON THE | | | BUILDING ORIENTATION. FBC ENERGY CONSERVATION 403.6 |
|