2015-01-28 11:39:261/28/2015
 PROJECT: 535 36TH ST
 PERMIT#: 14070394, REVISION TRACKING # 15010920
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 MAKE CORRECTIONS TO THE ELECTRICAL PLAN REVIEW
 DEFICIENCIES LISTED BELOW:
  
 1) NEC 210.63 SEE 210.8(A)(3), ONE 125VOLT,
 SINGLE-PHASE, 15 OR 20AMP GFI RECEPTACLE OUTLET SHALL
 BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT.
  
 2) NEC 440.14. DISCONNECTING MEANS SHALL BE LOCATED
 WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE
 DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED
 ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING
 EQUIPMENT.
  
 3) FBC-RESIDENTIAL 314 AND 315.WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
 4) NEC 210.52(D) AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE
 EDGE OF EACH BASIN. THE RECEPTACLE OUTLET SHALL BE
 LOCATED ON A WALL OR PARTITION THAT IS ADJACENT TO THE
 BASIN OR BASIN COUNTERTOP, OR INSTALLED ON THE SIDE OR
 FACE OF THE BASIN CABINET NOT MORE THAN (12 IN.) BELOW
 THE COUNTERTOP. SEE ALSO: 210.52(C)(3)
  
 5) NEC 250.94.AN INTERSYSTEM BONDING TERMINATION FOR
 CONNECTING INTERSYSTEM BONDING AND GROUNDING CONDUCTORS
 REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL
 TO ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  