| Plan Review Notes For Permit 15010907 |
| Permit Number |
15010907 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-27 13:57:56 | PROVIDE CORRECTIONS TO THE FOLLOWING ELECTRIC REVIEW | | | DEFICIENCIES : | | | | | | 1) PROVIDE A LARGE ENOUGH PLAN THAT IT IS LEGIBLE. | | | A.) WPB AMENDMENTS TO FBC 107.2.1 | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | B.) WPB AMENDMENTS TO FBC 107.2.1.4 | | | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE | | | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL | | | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | | | | 2) THE PLANS MUST BE SIGNED BY THE PERSON RESPONSIBLE | | | FOR THE DESIGN. | | | WPB AMENDMENTS TO FBC 107.2.1, AND FL SS 471, 668.001- | | | 668.006 | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | | | | | | | | | | |
|