| 2015-08-10 07:36:59 | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RDD REVIEW |
| | DATE: MON. AUG. 10/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) PRODUCT APPROVALS. |
| | |
| | 2A) 3RD REQUEST. GAF MODIFIED FL 13464- R0 THE ROOFING |
| | SUB-SYSTEMS TO BE APPLIED HAS NOT BEEN IDENTIFIED NOR |
| | THE ASSOCIATED PRESSURES. SEE APPENDIX SHEET 2 OF 13 |
| | NOTE 8 REQUIRES ENHANCED FASTENING BY A QUALIFIED |
| | DESIGN PROFESSIONAL. |
| | THE DESIGNER OF RECORD ON SHEET A1.0 HAS LISTED TABLE # |
| | 1 ON PLANS WHICH ALLOWS THE FOLOWING PRODUCTS (TABLE 1) |
| | MAKE UP THE SUBJECT SYSTEMS. NOTE TABLES 2A, 2B & 2C |
| | ARE STEEL DECKS WITH INSULATION NONE OF THE SUB-SYSTEMS |
| | HAVE BEEN IDENTIFIED FOR INSTALATION. THE DESIGNER OF |
| | RECORD HAS NOT INDICATED TO BE PICKED BY ROOFING |
| | CONTRACTOR AND REVIEWED BY THE DESIGNER OF RECORD |
| | BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. HAS NOT |
| | INDICATED THIS TO BE A DEFERRED SUBMITTAL. |
| | |
| | 3-5) COMPLIED. |
| | |
| | 6A) NEW COMMENT. SHEET A7.0 FOR EXTERIOR FINISHES |
| | INDICATES THE USE OF REYNOBOND ACM PANELS FOR THE |
| | EXTERIOR FINISH OF THE BUILDING. NO PRODUCT APPROVALS |
| | WERE SUBMITTED FOR THIS PRODUCT. 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: ACM PANELS/ AND OR MCM PANELS |
| | |
| | 6B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |