| Plan Review Notes For Permit 15010897 |
| Permit Number |
15010897 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-29 11:06:34 | PASS PROVISO | | | | | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE RTU CURB | | | TO | | | ROOF TIEDOWN AND RTU TO CURB TIEDOWN. PROVIDE THE | | | TYPE AND SIZE ANCHOR USED ON THE DETAIL. PER SECTION | | | 301.12 WIND RESISTANCE 2010 FBC (M) | | | 2) REFER TO SECTION 304.11 GUARDS 2010 FBC (M) | | | 3) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL | | | 2010 FBC (M) | | | 4) HOODS AND COOLERS REQUIRE SEPARATE APPLICATION | | | PLANS AND PERMIT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|