| Plan Review Notes For Permit 15010897 |
| Permit Number |
15010897 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-02 15:51:02 | PLAN DENIED | | | 1) RETURN AIR REQUIRED FOR OFFICE PER SECTION | | | 601.4 BALANCED RETURN AIR 2010 FBC (M) | | | 2) PROVIDE A DETAIL FROM THE ENGINEER ON | | | CURB TO ROOF TIE DOWN AND RTU TO CURB | | | TIE DOWN .PROVIDE TYPE SIZE AND SPACING | | | OF ANCHOR. PER SECTION 301.12 WIND RESISTANCE | | | FBC (M) 2010 | | | 3) SEPARATE APPLICATION PLAN AND PERMIT REQUIRED | | | FOR HOODS AND COOLERS . |
|