| Plan Review Notes For Permit 15010897 |
| Permit Number |
15010897 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-30 11:34:41 | GAS | | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND | | | LABELED PER 2010 FL. GAS CODE SEC. 301.3. | | | 2) REFER TO THE APPLICABLE PIPE SIZING TABLE ON SHT.P-2 | | | FROM THE 2010 FGC THAT WAS USED TO SIZE THE GAS | | | PIPING.FGC SEC.402.3. | | | 3) SHOW THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING | | | FROM THE POINT OF DELIVERY. 402.4.1. | | | 4) INDICATE THE TYPE OF PIPE BEING USED FOR THE GAS | | | SYSTEM. WPB AMEND.TO 2010 FBC SEC.107.2.1. | | | 5) INDICATE THE PIPE SIZE OF THE DROPS TO THE | | | EQUIPMENT. WPB AMEND.TO 2010 FBC SEC.107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|