Plan Review Notes
Plan Review Notes For Permit 15010897
Permit Number 15010897
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-02-10 17:28:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE REVISE THE EDITION OF THE FLORIDA LIFE SAFETY
 CODE TO 2012.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANY LOADS,
 EXIT PATHS, COMMON PATHS OF TRAVEL, EXIT PATH
 DIMENSION, EIXTS, EXIT DOORS, AND FIRE EXTINGUISHERS
 LOCATIONS.
  
 PROVIDE CONSTUCTION COMMENTS/NOTES ON THE PLAN
 INDICATING THE INSTALLATION OF A NFPA 96 COMPLIANT HOOD
 SYSTEM TO BE SUBMITTED THROUGH SEPARATE SHOP DRAWINGS.
  
 PROVIDE CONSTRUCTION COMMENTS/NOTE ON THE PLAN
 INDICATING THE INSTALLATION OF A NFPA COMPLIANT HOOD
 SUPPRESSION SYSTEM TO BE SUBMITTED THROUGH SEPARATE
 SHOP DRAWINGS.
  
 PROVIDE INDICATION THE THE BUILDING ADDRESS WILL BE
 VISIBLE FROM THE STREET. NUMBERS SHALL BE ATTACHED TO
 THE BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081, STRUCTURES WITH LIGHT FRAME
 FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED WITH
 A SIGN AFFIXED TO THE BUILDING. PROVIDE INDICATIONS
 THAT A MALTESE CROSS 8-INCHES WIDE AND 8-INCHES TALL
 AND BE OF A BRIGHT RED REFLECTIVE COLOR AND BEAR THE
 APPROPRIATE LETTER R/F/RF DESIGNATION SHALL BE
 INSTALLED WITHIN 24" OF THE FRONT DOOR.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION NFPA 101, 7.2.1.5.9, THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
  